Error : Hot water securing

If the error 102 message is displayed on the AC•THOR /AC•THOR 9s , this means that the hot water securing function is active, but no temperature sensor has been connected or activated yet.

To correct this error, connect the sensor to the AC•THOR and activate it via the display.

To do this, click on settings (gearwheel symbol), scroll to the item "sensors" and select it.

You will then see the serial number of the connected sensor and its current temperature on the display. Click once on this line. Now the sensor number is displayed to the right of the displayed temperature. This sensor is now active. Finally, save the setting.

TIP: If the optional temperature safeguard is not used, the heat generator has a thermostat and you only want to use excess energy anyway, then the installation of the temperature sensor is not necessary at all!

Our "Support" section offers many useful practical tips that will help you install and commission our solutions.

Furthermore, you will learn about all the most important innovations of my-PV products.

More articles

Referenze

Calore fotovoltaico in due versioni per acqua calda e riscaldamento

Un impianto fotovoltaico collegato alla rete e uno autonomo producono acqua calda e riscaldamento in Foresta Nera.

Leggi di più...
reduxi Logo

Partner

Reduxi ora compatibile con my-PV

Acqua calda intelligente con surplus PV: Reduxi ora compatibile con i dispositivi my-PV.

Leggi di più...
Five white my-PV company cars in front of the building with wooden facade, logo, and solar panels.

Azienda

Auto elettriche presso my-PV

Vediamo il futuro non solo nella tecnologia degli edifici (solare-)elettrici, ma anche nel settore della mobilità.

Leggi di più...