Support AC•THOR / AC•THOR s Firmware a Changes
Support: AC•THOR / AC•THOR 9s Firmware a0020410 changes
- All signal sources, including those that were previously only selectable via the web interface, can now be set on the display.
- The frequency mode is no longer a separate operating mode. Instead, frequency control can be selected as a signal source. Thus, the operating modes M1 to M7 can now be used in AC off-grid systems.
- A firmware update on a unit in "M8 frequency mode" automatically switches it to "M1 hot water" operating mode and "frequency" is set as the signal source.
- New signal source "Fronius Gen24 Manual" added.
- Correction for operating mode M7. The PWM output signal works correctly again.
- The heat pump operating mode M4 can now also be used if no meter value is known at the feed-in point. The power specifications, e.g. via Modbus TCP, are sufficient information for the control.
- The combination with charging columns from KEBA and Eaton is now also possible if no meter value is known at the feed-in point. The power specifications, e.g. via Modbus TCP, are sufficient as information for the control.
- Further information here:/(German)
- Optimising the data connection with my-PV.LIVE
- Here you will find the latest
More articles
Referenties
Zonne-elektrische warmwateroplossing in een tweegezinswoningTweegezinswoning in NRW gebruikt zijn 24,75 kWp PV-systeem met cloudvrij smarthome en AC ELWA 2 voor warm water.
Lees meer...Partner
Nieuwe compatibiliteitspartner SAX PowerDe batterijopslagsystemen van SAX Power zijn nu compatibel met de zonne-elektrische oplossingen van my-PV!
Lees meer...Algemeen
De juiste mijn-PV oplossing – eenvoudig gevonden!De mijn-PV Check is nu beschikbaar en helpt u bij het plannen van uw systeem.
Lees meer...