AC•THOR 9s – Operation with 3 single-phase heating elements

Our "Support" section offers many practical tips that will help you with the installation and commissioning of our devices.

The load control of 3 single-phase heating elements is a special form of operating mode M1 for hot water.

CAUTION:

This is to be clearly distinguished from operating mode M2 "Layer Charging," where load control is switched to another 3-phase consumer using an external opener and a closer!

The following instructions from the operating manual are important:

Solution

The regular operation for 3 single-phase heating elements can be set with a single adjustment. Simply switch the "Load Priority" accordingly under "Settings" (gear symbol).

Wist u dat?

Tip: Connect the topmost heating element to the control output OUT-3 of the AC•THOR 9s. If you accidentally did not follow the order, simply switch the consumption plugs. This saves rewiring!

More articles

Partner

Compatibiliteit met Eniris

De zonne-elektrische oplossingen van my-PV zijn nu ook compatibel met de Eniris SmartgridOne.

Lees meer...
Flowchart guiding photovoltaic system choice, showing options for using electricity for household power, water heating, or both, with product recommendations.

Algemeen

How do I find the right my-PV product?

Do you have a rooftop photovoltaic system with enough surplus energy? Then it’s time to consider a my-PV product.

Lees meer...
A modern two-story house with a green and white van parked in the driveway, surrounded by greenery and a brick wall, under a partly cloudy sky.

Referenties

Belgisch gezinshuis vertrouwt op de AC•THOR

Belgische familie verhoogt zelfverbruik van zonne-energie tot 74% met AC•THOR, allemaal zonder batterijopslag.

Lees meer...